[40882] Artykuł: Estimation of Fault Transverse Impedance and the Distance to Fault Location in an Open Coaxial Power Cable on the Basis of Measurement of Input ImpedancesCzasopismo: International Review of Electrical Engineering (IREE) Tom: 8, Zeszyt: 3ISSN: 1827-6660 Opublikowano: 2013 Autorzy / Redaktorzy / Twórcy
Grupa MNiSW: Publikacja w recenzowanym czasopiśmie wymienionym w wykazie ministra MNiSzW (część B) Punkty MNiSW: 10 Keywords: Fault Location  Fault Localization  Coaxial Cable  Fault Transverse Impedance  Fault Distance  Input Impedance  |
The article presents the original method of calculating the transverse impedance damage and the distance to a fault location in XRUHKXS 1×120RMC/50 the power cable with a local weakening of insulation. The method is based on the measurements of input impedance of the cable in an open state at both ends to determine the fault transverse impedance and the distance to the fault location. The proposed method is non-destructive and can be used remotely as a preliminary method of fault localization. The method was compared with time-domain reflectometry. Both numerical and experimental verifications confirm its effectiveness.